Product Overview


The signal isolator functions as a safety barrier, providing intrinsically safe power supply and signal conversion for field intrinsically safe devices. The isolator supports four types of signal conversion to satisfy various application requirements.

The signal isolator integrates intrinsically safe power output, dual-channel CAN bus signal acquisition or dual-channel current signal acquisition, and signal output (selectable from RS485, CAN2.0B, or current signal output). It features a compact structure and is equipped with an OLED display and buttons for parameter configuration, making installation and maintenance convenient. When used together with intrinsically safe transmitters, it can be widely applied in underground or surface coal mine equipment for the measurement and control of pressure, temperature, level, differential pressure, flow, tension/compression force, and other parameters. This product must be installed and used in a safe area or within a flameproof enclosure. It adopts a standard 35 mm DIN rail mounting method.

The product explosion-proof marking is [Ex ib Mb] I.



Key Technical Specifications

Item

Technical Parameters

Operating Power Supply

24VDC(standard); operating range:(18~27)VDC

Power Output

400mA DC

Input Signal

Two CAN2.0B signals or two (4~20) mA current signals.

Output Signal

(4~20) mA current signal; CAN2.0B signal; RS485 signal

Product Types

• KJA-09-I: CAN2.0B input signal to RS485 output signal (input voltage 24 V, output voltage 9 V);

• KJA-12-II: (4–20) mA current input signal to (4–20) mA current output signal (input voltage 24 V, output voltage 12 V);

• KJA-12-III: (4–20) mA current input signal to CAN2.0B output signal (input voltage 24 V, output voltage 12 V);

• KJA-12-IV: (4–20) mA current input signal to RS485 output signal (input voltage 24 V, output voltage 12 V).

Intrinsically Safe Parameters

Um=24V;Uo=9V/12V;Io=600mA/450mA;Po=1.4W;Co=200uf;Lo=2mH.

Protection Rating

IP41 (compliant with GB/T 4208)

Overall Size

46x95x47



Model and Specifications

KJA-09-I;KJA-12-II;KJA-12-III;KJA-12-IV.


Downloads

Related Products

  • KJA Series Mining Intrinsically Safe Signal Isolator
  • BAM Series Mining Intrinsically Safe Power Module
  • KDY Series Mining Explosion-proof & Intrinsically Safe DC Power Supply
  • GUD20 Mining Explosion-proof Encapsulated Inductive Displacement Sensor

Contact Us

If you're interested or have any questions please don't hesitate to reach out. Send us a message anytime, and we'll respond promptly!

Submit